Description
3.2 Measuring inputs
SENTRON PAC3200
22
Manual, 02/2008, A5E01168664B-04
Input and output
●
Multifunctional digital input for tariff changing, demand period synchronization, status
monitoring or acquisition of energy pulses from third-party devices.
●
Multifunctional digital output, programmable as energy pulse output for active energy or
reactive energy pulses, for showing the direction of rotation, indicating the working hours
of the SENTRON PAC3200, outputting limit violations, or as a switching output for remote
control via PC.
Protection
Password protection on the device by means of 4-character code.
See also
Measured variables (Page 24)
Connection (Page 73)
Technical data (Page 157)
3.2
Measuring inputs
Current measurement
CAUTION
AC current measurement only
The device is not suitable for measuring DC current.
SENTRON PAC3200 is designed for:
●
Measuring current of 1 A or 5 A for connecting standard current transformers. Each
current measuring input can take a continuous load of 10 A (max. 300 V). Surge
withstand capability is possible for currents up to 100 A and a duration of 1 s.
Voltage measurement
CAUTION
AC voltage measurement only
The device is not suitable for measuring DC voltage.
Summary of Contents for SENTRON PAC3200
Page 16: ...Introduction 1 6 Further documentation SENTRON PAC3200 16 Manual 02 2008 A5E01168664B 04 ...
Page 90: ...Connection 6 4 Connection examples SENTRON PAC3200 90 Manual 02 2008 A5E01168664B 04 ...
Page 124: ...Operator control 8 2 Operator input steps SENTRON PAC3200 124 Manual 02 2008 A5E01168664B 04 ...
Page 125: ...Operator control 8 2 Operator input steps SENTRON PAC3200 Manual 02 2008 A5E01168664B 04 125 ...
Page 126: ......
Page 178: ...Glossary SENTRON PAC3200 178 Manual 02 2008 A5E01168664B 04 ...
Page 182: ...Index SENTRON PAC3200 182 Manual 02 2008 A5E01168664B 04 ...