Parameterize
9.2 Parameterizing the operator interface
SENTRON PAC3200
144
Manual, 02/2008, A5E01168664B-04
LIMIT 0, 1, 2, 3, 4, 5
Menu selection of the limits Each limit has the
following properties:
MONITORING
Activation of limit monitoring.
ON/OFF switch: ON / OFF.
ON: Limit monitoring switched on.
OFF: Limit monitoring switched off.
Default: OFF
Figure 9-20 "LIMIT 0" device setting
SOURCE
Monitored data source.
Range:
V L1, V L2, V L3,
V L12, V L23, V L31,
I L1 / I L2 / I L3
VA L1 / VA L2 / VA L3
W L1 / W L2 / W L3
VAR L1 / VAR L2 / VAR L3
PF L1, PF L2, PF L3,
THD-V L1, THD-V L2, THD-V L3,
THD-I L1, THD-I L2, THD-I L3,
FREQ.,
V LN AVG, V LL AVG, I AVG,
ΣVA, ΣW, ΣVAR,
TOTAL PF
UNBAL V, UNBAL I,
Default:
V L1
MODE
Relational operators
GREATER THAN, LOWER THAN the value in
the VALUE field.
Default operator: GREATER THAN
VALUE
Monitored threshold.
Default: 0 V, corresponding to "SOURCE V L1"