Parameterize
9.2 Parameterizing the operator interface
SENTRON PAC3200
Manual, 02/2008, A5E01168664B-04
137
9.2.6
Integrated I/O
Device settings for using the digital input and output.
Call: "SETTINGS > INTEGRATED I/O".
Figure 9-8
"INTEGRATED I/O" device setting
DIGITAL OUTPUT
Figure 9-9
"DIGITAL OUTPUT" device setting
ACTION
Method of using the digital output:
OFF:
The digital output is switched off.
DEVICE ON:
The digital output is switched on.
REMOTE OUTPUT.
The digital output is controlled by remote
access, e.g. SEAbus, SEAbus TCP,
PROFIBUS DP, Modbus RTU,
Modbus TCP.
ROTATION:
The digital output is switched on by a left-
rotating electrical field and remains active
while the direction of rotation of the field
remains unchanged.
LIM.VIOLATION:
The digital output is switched on by a limit
violation and remains active while the limit
violation prevails.
The field "DIGITAL OUTPUT > SOURCE"
selects the limit to be monitored. The
definition of the limit is stored in
"ADVANCED > LIMITS".
Summary of Contents for SENTRON PAC3200
Page 16: ...Introduction 1 6 Further documentation SENTRON PAC3200 16 Manual 02 2008 A5E01168664B 04 ...
Page 90: ...Connection 6 4 Connection examples SENTRON PAC3200 90 Manual 02 2008 A5E01168664B 04 ...
Page 124: ...Operator control 8 2 Operator input steps SENTRON PAC3200 124 Manual 02 2008 A5E01168664B 04 ...
Page 125: ...Operator control 8 2 Operator input steps SENTRON PAC3200 Manual 02 2008 A5E01168664B 04 125 ...
Page 126: ......
Page 178: ...Glossary SENTRON PAC3200 178 Manual 02 2008 A5E01168664B 04 ...
Page 182: ...Index SENTRON PAC3200 182 Manual 02 2008 A5E01168664B 04 ...