Description
3.5 Digital inputs and outputs
SENTRON PAC3100
Manual, 07/2009, A5E02385159B-01
23
3.4.2
Energy counters
Energy counters
SENTRON PAC3100 has energy counters for counting
●
Active energy import
●
Active energy export
●
Reactive energy import
●
Reactive energy export
The device also calculates the energy balance
●
Active energy balance
●
Reactive energy balance
The energy balance is calculated from: Import minus export.
Availability
Two of the 6 variables can be represented on the display and read out via the interface. The
selection can be made when parameterizing the device.
3.4.3
Behavior in the case of power failure and power restore
After a power failure, the device starts back at zero with the calculation of the power demand
of the total active power and total reactive power.
Counter statuses and maximum/minimum values are written from the volatile to the non-
volatile memory at the following intervals:
Counter values
Every 5 mins.
Maximum/minimum values
Every 5 secs., if available
3.5
Digital inputs and outputs
The SENTRON PAC3100 has:
●
2 digital inputs
●
2 digital outputs
Summary of Contents for SENTRON PAC3100
Page 10: ...Table of contents SENTRON PAC3100 10 Manual 07 2009 A5E02385159B 01 ...
Page 38: ...Mounting 5 3 Deinstallation SENTRON PAC3100 38 Manual 07 2009 A5E02385159B 01 ...
Page 104: ...Service and maintenance 10 5 Disposal SENTRON PAC3100 104 Manual 07 2009 A5E02385159B 01 ...
Page 118: ...Dimensional drawings SENTRON PAC3100 118 Manual 07 2009 A5E02385159B 01 ...
Page 142: ...Appendix A 3 Correction sheet SENTRON PAC3100 142 Manual 07 2009 A5E02385159B 01 ...
Page 146: ...List of abbreviations C 1 Abbreviations SENTRON PAC3100 146 Manual 07 2009 A5E02385159B 01 ...
Page 148: ...Glossary SENTRON PAC3100 148 Manual 07 2009 A5E02385159B 01 ...
Page 152: ...Index SENTRON PAC3100 Manual 07 2009 A5E02385159B 01 152 ...