Technical specifications
8.1 Technical specifications
PAC2200CLP
80
Equipment Manual, 06/2021, L1V30820585B-02
Digital output
Digital output
Number
1
Type
Passive
Design/function
Switching output or pulse output
Rated voltage
0 ... 30 V DC, typical 24 V DC (SELV or PELV sup-
ply)
Output current
For signal "1"
Depends on the load and the external power sup-
ply
Continuous load
≤50
mA (thermal overload protection)
Transient overload
≤130
mA for 100 ms
For signal "0"
≤0.2
mA
Internal resistance
30
Ω
Overvoltage category
OVC I
Pulse output function
Standard for pulse emitter
Signal characteristics in accordance with
IEC 62053-31
Adjustable pulse duration
30 … 500 ms
Min. settable time frame
10 ms
Max. switching frequency
17 Hz
Short-circuit protection
Yes
Communication
Ethernet interface (optional)
Protocols
Modbus TCP; web server (HTTP); SNTP; DHCP
Ethernet connection
RJ-45
Data rate
10 / 100 Mbps