Appendix
A.1 Modbus TCP
PAC2200CLP
108
Equipment Manual, 06/2021, L1V30820585B-02
Offset
Number of
registers
Name
Unit
Format
Value range
Access
3 = Direction of rota-
tion
5 = Energy pulse
50041
2
"Energy pulse" mode
-
unsigned long
0 = Import kWh
RW
1 = Export kWh
2 = Import kVARh
3 = Export kVARh
50043
2
Pulses per pulse unit
-
unsigned long
1 ... 4000
RW
50045
2
Pulse length
ms
unsigned long
30 ... 500
RW
50147
2
Timeout digital output
s
unsigned long
0 = AUS
0.1 ... 18000 = Output is
reset after expiry of the
time, provided there is no
operator input.
RW
50237
2
Pulse unit
kWh
unsigned long
0 = 1 kWh / kvarh
RW
1 = 10 kWh / kvarh
2 = 100 kWh / kvarh
3 = 1000 kWh / kvarh
A.1.9
Modbus communication parameters with the function codes 0x03, 0x04
and 0x10
Addressing the communication parameters
Table A- 10 Communication parameters
Offset Number of
registers
Name
Unit
Format
Applicable
Modbus func-
tion codes
Value range
Access
62991 2
DHCP ON/OFF
-
unsigned long
•
0x03
•
0x04
•
0x10
0 = DHCP OFF
1 = DHCP ON
RW
62993 2
SNTP server IP ad-
dress
-
unsigned long
•
0x03
•
0x04
•
0x10
0 ... FFFFFFFFh
RW
62995 2
SNTP client mode
-
unsigned long
•
0x03
•
0x04
•
0x10
0 = SNTP client
OFF
1 = SNTP active
client
2 = SNTP broad-
cast client
RW
Summary of Contents for SENTRON PAC2200CLP
Page 1: ......
Page 2: ......
Page 8: ...Table of contents PAC2200CLP 6 Equipment Manual 06 2021 L1V30820585B 02 ...
Page 14: ...Introduction 1 6 Risk of manipulation PAC2200CLP 12 Equipment Manual 06 2021 L1V30820585B 02 ...
Page 78: ...Service and maintenance 7 4 Warranty PAC2200CLP 76 Equipment Manual 06 2021 L1V30820585B 02 ...
Page 129: ......
Page 130: ......