Description
2.5 Communication
PAC2200
Equipment Manual, 12/2019, L1V30415167B-03
29
2.5.3.1
Three-phase connection (3P4W)
The measurement data is presented on three pages (Mapping 0) and on four pages
(Mapping 1). Multipage-capable masters can read out all three or four pages.
As an example, the coding of the data record with ID 13 (connection type 3P4W, Mapping 1,
i.e. version 32) is more accurately explained in the RSP_UD2 response datagram (see also
M-BUS specification):
Measured variable ID 13: L2 active energy export tariff 2
BYTE No.
Coding
Description
Byte 1
0x86
DIF value format INT48 -> Integer 6 bytes length
Byte 2
0x20
DIFE tariff 2
Byte 3
0x83
VIF active energy / unit Wh
Byte 4
0xBC
VIFE export
Bytes 5-6
0xFC 0x02
VIFE phase L2
Bytes 7-12
XX XX XX XX XX XX
Integer value of measured variable
All measurement data that can be read out via the M-BUS are listed in the following table.
ID
Measured variable
Length
(bits)
Format
Unit
1
Secondary total active energy (MID register)
48
INT48
Wh
2
Total active energy import tariff 1
48
INT48
Wh
3
Total active energy import tariff 2
48
INT48
Wh
4
Total active energy export tariff 1
48
INT48
Wh
5
Total active energy export tariff 2
48
INT48
Wh
6
L1 active energy import tariff 1
48
INT48
Wh
7
L1 active energy import tariff 2
48
INT48
Wh
8
L1 active energy export tariff 1
48
INT48
Wh
9
L1 active energy export tariff 2
48
INT48
Wh
10
L2 active energy import tariff 1
48
INT48
Wh
11
L2 active energy import tariff 2
48
INT48
Wh
12
L2 active energy export tariff 1
48
INT48
Wh
13
L2 active energy export tariff 2
48
INT48
Wh
14
L3 active energy import tariff 1
48
INT48
Wh
15
L3 active energy import tariff 2
48
INT48
Wh
16
L3 active energy export tariff 1
48
INT48
Wh
17
L3 active energy export tariff 2
48
INT48
Wh
18
Total active power
32
FLOAT32
W
19
Active power L1
32
FLOAT32
W
20
Active power L2
32
FLOAT32
W
21
Active power L3
32
FLOAT32
W
22
Voltage L1-N
32
FLOAT32
V
23
Voltage L2-N
32
FLOAT32
V
24
Voltage L3-N
32
FLOAT32
V
Summary of Contents for SENTRON PAC2200
Page 1: ......
Page 2: ......
Page 8: ...Table of contents PAC2200 6 Equipment Manual 12 2019 L1V30415167B 03 ...
Page 14: ...Introduction 1 6 Risk of manipulation PAC2200 12 Equipment Manual 12 2019 L1V30415167B 03 ...
Page 40: ...Description 2 5 Communication PAC2200 38 Equipment Manual 12 2019 L1V30415167B 03 ...
Page 54: ......
Page 84: ...Service and maintenance 7 5 Warranty PAC2200 82 Equipment Manual 12 2019 L1V30415167B 03 ...
Page 96: ...Technical specifications 8 2 Labeling PAC2200 94 Equipment Manual 12 2019 L1V30415167B 03 ...
Page 129: ......
Page 130: ......