MODBUS communication
10.4 Data library
3KC ATC6500 transfer control device
200
Manual, 05/2019, L1V30538268002A-01
③
Key press simulation
The following values must be sent to the address 2F0AH in order to simulate the
corresponding key press:
Bit
Meaning
0
▲
key
1
Key MAN
2
►
key
3
<< key
4
Key TEST
5
AUT key
6
Key OFF
7
OPEN key
8
>> key
9
▼
key
10
✓
key
11
◄
key
12
CLOSE key
④
Execution of the Commands menu
The following values between 0 and 15 must be sent to the address 2FF0H in order to
execute the corresponding command:
Bit
Meaning
0
Reset maintenance 1
1
Reset maintenance 2
2
Reset maintenance operations 1
3
Reset maintenance operations 2
4
Reset counter CNTx
5
Reset status limit threshold LIMx
6
Reset hours counter Source 1
7
Reset hours counter Source 2
8
Reset hours counter Breaker 1
9
Reset hours counter Breaker 2
10
Reset breaker operation
11
Reset event log
12
Restore default parameters
13
Save parameters in backup memory
14
Reload parameters from backup memory
15
Forced changeover I / O
16
Reset A03 - A04 alarms
17
Simulates priority source failure