7.3 Connection of Siemens SENTRON switching devices
3KC ATC6500 transfer control device
Manual, 05/2019, L1V30538268002A-01
107
7.3.4
Typical operating times of the Siemens SENTRON switching devices (IEC only)
The following typical operating times can be achieved with the ATC and Siemens circuit
breakers.
Note
Checking
The tables below contain typical operating values. Check the operating times of the
respective total installation under real conditions.
Note:
The operating times of the tie breaker can be obtained from the manual or the catalog of the
relevant circuit breaker. Note the additional interlock time for the tie breaker control in
accordance with parameter P02.30 (see chapter P02 (Page 162)).
Operating times of the 3VA
Unit
2 x 3VA11
(160A) + 2x MO
2 x 3VA12 (250A)
+ 2x MO
3VA13 (400A) +
2x MO
2 x 3VA14 (630A)
+ 2x MO
Time I-O
ms
800
800
1400
1400
Time II-O
ms
800
800
1400
1400
Time I-O-II (for min parameter)*
ms
1700
1700
3200
3200
* includes the minimum delay time from Source 1 to Source 2 of 100 ms (see parameter P07.n.02)
Unit
2 x 3VA21
+ 2x MO
2 x 3VA21
+ 2x SEO
2 x 3VA22
+ 2x MO
2 x 3VA22
+ 2x SEO
2 x 3VA23
+ 2x MO
2 x 3VA24
+ 2x MO
2x 3VA27
(1600 A)
Time I-O
ms
1000
80
1000
80
1400
1400
20
Time II-O
ms
1000
80
1000
80
1400
1400
20
Time I-O-II (for min
parameter)*
ms
2100
260
2100
260
3200
3200
170
* includes the minimum delay time from Source 1 to Source 2 of 100 ms (see parameter P07.n.02)
Operating times of the 3WL
Unit
2x 3WL10
2x 3WL11
2x 3WL12
2x 3WL13
Time I-O
ms
20
73
73
73
Time II-O
ms
20
73
73
73
Time I-O-II (for min parame-
ter)*
ms
170
253
273
273
* includes the minimum delay time from Source 1 to Source 2 of 100 ms (see parameter P07.n.02)