Connection
7.2 Connection of the power supply
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01
75
Network/generator transfer
The output Control Generator 2 must then be programmed in such a way that the generator
is started when the ATC6300 is de-energized.
Connection
Parameter
Output type
Setting
OUT (3) 22 - 23
P11.03.01
NOR
Control Generator 2
Generator/generator transfer
The output Control Generator 2 must then be programmed in such a way that the generator
is started when the ATC6300 is de-energized.
Connection
Parameter
Output type
Setting
OUT (3) 22 - 23
P11.03.01
NOR
Control Generator 2
OUT (2) 11 - 12
P11.02.01
REV
Control Generator 1
7.2.6
Recommended implementation for gen-set application (without power supply by
means of a DC source)
If gen-sets are used, the following connection is recommended:
The auxiliary power supply is controlled by the ATC6300. The use of the dual network
connection accessory is optional.
Connection
Parameter
Setting
OUT (1) 9 - 10
P11.01.01
Line 1 status
Network/generator transfer
The output Control Generator 2 must then be programmed in such a way that the generator
is started when the ATC6300 is de-energized.
Connection
Parameter
Output type
Setting
OUT (3) 22 - 23
P11.03.01
NOR
Control Generator 2