Product description
4.5 Display pages of the ATC6300
3KC ATC6300 transfer control device
26
Manual, 03/2018, L1V30535632002A-01
It shows
●
the threshold values of the voltage between L-L and between L-N (if set)
●
the threshold values of the minimum and maximum frequency
If a threshold value is exceeded/undershot, it is shown with a black background, which
means that it is possible to check in real time in the Control Thresholds menu which
parameter of the voltage supply is causing problems.
Alarms status
①
Active alarm
The Alarms Status submenu lists all possible alarms of the ATC6300. If an alarm is active
the corresponding alarm has a black background.
Statistics
①
Line 2
②
Counter of the switching operations in the automatic mode for Line 2
③
Alarm counter A04
④
Time during which the line is within the defined thresholds
⑤
Elapsed time in which the load has zero current
⑥
Counter of the deactivation processes
⑦
Time during which the line was outside the defined thresholds
⑧
Time in which the power supply was maintained by Line 1
⑨
Counter of the switching operations in the manual mode for Line 1
⑩
Line 1
The transfer behavior is shown in the Statistics submenu.