Accessories
12.1 Expansion modules
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01
189
12.1.5.2
Technical specifications
Power supply
Supply voltage
5 V DC (supplied through the ATC6300)
Current consumption (max.)
200 mA
Power loss (max.)
1.0 W
Digital inputs
Number of digital inputs
2
Input type
Negative
Input current
7 mA
Maximum frequency
2000 Hz (if the input is configured as a counter)
50 Hz (if input is configured as status)
Input signal delay
≥
50 ms
Impulse withstand voltage U
imp
4 kV
Operating frequency impulse with-
stand voltage
2 kV
Control terminal COM
Auxiliary power supply at control
terminal COM
5 V DC
Relay outputs
Contact type
2x 1 NO contacts
Rated contact current
(IEC 60947-5-1)
AC1 5 A 250 V
DC1 2 A 30 V
AC15 0.75 A 250 V
UL Rating
C300, 2 A 30 V DC, 5 A 250 V AC pilot duty
Operational voltage (maximum)
250 V AC
Mechanical/electrical endurance
(cycle)
3x10^6 / 1x10^5
Impulse withstand voltage U
imp
4 kV
Insulation voltage U
i
250 V AC
Operating frequency impulse with-
stand voltage
2 kV
Connection
Connecting terminals
Removable / plug-in
Cable cross-section (min-max)
0.2 … 2.5 mm
2
(AWG 24 ... 12)
Cable cross-section (min-max)
acc. to UL 508
0.75 … 2.5 mm
2
(AWG 18 ... 12)
Tightening torque
0.5 Nm (4.5 lbf-in)
Ambient conditions
Operating temperature
-20 … +60 °C
Storage temperature
-30 … +80 °C
Relative humidity
< 80 % (IEC / EN 60068-2-70)
Maximum degree of pollution
2