MODBUS communication
11.6 Data library
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01
163
⑧
The 16 bits of the status Function Messages on the display for the address 207Bh have
the following meaning:
Bit
Messages on display
0
Start generator 1
1
Start generator 2
2
Cooling generator 1
3
Cooling generator 2
4
Counter (2 → 1)
5
Load transfer 1 → 2
⑨
The 16 bits of the status General Status ATC for the address 207Ch have the following
meaning:
Bit
General Status ATC
0
OFF / RESET operating mode
1
MAN operating mode
2
AUT operating mode
3
TEST operating mode
4
Error
5
AC supply present
6
DC supply present
7
Global alarm enabled
8-15
Not used