MODBUS communication
11.6 Data library
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01
157
11.6
Data library
11.6.1
Measured values (use with MODBUS function 03 and 04)
Address
Measured value
Unit
Format
02h
Voltage of Line 1 L1-N
V
Unsigned long
04h
Voltage of Line 1 L2-N
V
Unsigned long
06h
Voltage of Line 1 L3-N
V
Unsigned long
08h
Voltage of Line 1 L1-L2
V
Unsigned long
0Ah
Voltage of Line 1 L2-L3
V
Unsigned long
0Ch
Voltage of Line 1 L3-L1
V
Unsigned long
0Eh
Voltage of Line 2 L1-N
V
Unsigned long
10h
Voltage of Line 2 L2-N
V
Unsigned long
12h
Voltage of Line 2 L3-N
V
Unsigned long
14h
Voltage of Line 2 L1-L2
V
Unsigned long
16h
Voltage of Line 2 L2-L3
V
Unsigned long
18h
Voltage of Line 2 L3-L1
V
Unsigned long
1Ah
Frequency Line 1
Hz /10
Unsigned long
1Ch
Frequency Line 2
Hz /10
Unsigned long
1Eh
Battery voltage (DC source)
V DC / 10 Unsigned long
20h
Total operation time
s
Unsigned long
22h
Time Line 1 OK
s
Unsigned long
24h
Time Line 2 OK
s
Unsigned long
26h
Time Line 1 not OK
s
Unsigned long
28h
Time Line 2 not OK
s
Unsigned long
2Ah
Time Line 1 breaker closed
s
Unsigned long
2Ch
Time Line 2 breaker closed
s
Unsigned long
2Eh
Total time breaker open
s
Unsigned long
30h
Not used
--
Unsigned long
32h
Number of operating cycles of Breaker Line 1
in AUT
no.
Unsigned long
34h
Number of operating cycles of Breaker Line 2
in AUT
no.
Unsigned long
36h
Number of operating cycles of Breaker Line 1
in MAN
no.
Unsigned long
38h
Number of operating cycles of Breaker Line 2
in MAN
no.
Unsigned long
3Ah
Number of alarms for changeovers of Breaker
1
no.
Unsigned long
3Ch
Number of alarms for changeovers of Breaker
2
no.
Unsigned long
3Eh
Not used
--
Unsigned long