Parameterization
9.3 Parameters
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01
137
P09 –
Automatic
test
Designation on ATC
display
Description
Unit
Default Range
P09.12
Auto Test duration
TEST duration
– Duration of the periodic test in minutes.
min
10
1-600
P09.13
Auto Test with load Automatic TEST with load changeover
– Load management during the execution of
the periodic test:
OFF = The load is not switched.
With load = Enables the switching the load from
network to generator.
Dummy load = The load simulation is switched
on, the system load is not switched.
OFF
OFF
With load
Dummy load
9.3.10
P10 - Digital inputs
This menu is divided into 14 sections. These refer to 6 possible digital inputs INP1…INP6
that can be managed directly by the ATC6300, and a further 8 inputs that can be managed
by the ATC6300 via the expansion modules.
P10
Digital inputs
(INPn,
n=1…14)
Designation on
ATC display
Description
Unit
Default Range
P10.n.01
Input function
Function of the INPn input
– Selects the function of the selected input (see
table "Functions of the programmable inputs" in
chapter Digital inputs INPx (Page 107)).
-
(Page 108)
P10.n.02
Channel number Function index (x)
– Index that is possibly assigned to the function
programmed in the previous parameter. Exam-
ple: If the input function is set to Cxx command
menu execution, and this input is to perform
command C07 in the command menu, then
P10.n.02 must be set to the value 7.
OFF
OFF / 1 … 99
P10.n.03
Contact type
Contact type
– Select the contact type: NO (normally open)
or NC (normally closed)
NO
NO / NC
P10.n.04
Delay ON
Closing delay
– Contact closing delay for selected input.
s
0.05
0.00 - 600.00
P10.n.05
Delay OFF
Opening delay
– Contact opening delay for selected input.
s
0.05
0.00 - 600.00