Parameterization
9.3 Parameters
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01
125
9.3.5
P05 - Changeover
P05
Changeo-
ver
Designation on ATC
display
Description
Unit
Default
Range
P05.01
Application type
Type of application
– This parameter specifies the type of applica-
tion and facilitates the management of the cor-
responding input / output signals.
U-G = Utility (network) / Generator
U-U = Utility (network) / Utility (network)
G-G = Generator / Generator
U-G
U-G
U-U
G-G
P05.02
Priority line
Selecting the priority line
– Specifies the priority line. It defines the line
through which the loads are supplied, if both
lines are present.
- 1 -
-1- Line 1
-2- Line 2
P05.03
Line 1 -> 2 interlock Line 1
→ Line 2 interlock time
– Delay that elapses between the disconnection
of breaker Line 1 and the opening command for
breaker Line 2. For example, if the breaker Line
1 is opened, there is a wait time of 6 seconds in
accordance with default settings for an opening
command to be sent to the breaker Line 2.
s
6.0
0.1 ... 1800.0
P05.04
Line 1 -> 2 interlock
Line 1 ←
Line 2 interlock time
– Delay that elapses between the disconnection
of breaker Line 2 and the opening command for
breaker Line 1.
s
6.0
0.1 ... 1800.0
P05.05
Changeover re-
sponse
Changeover response
– This parameter defines the general conditions
for a changeover.
A selection can be made between OBP (Open
before presence) and OAP (Open after pres-
ence).
OBP
OBP
1)
OAP
2)
P05.06
Feedback delay
Maximum time for switch control -
Alarm delay A03 – A04
– If a switching device is not in the correct posi-
tion within this time following an ON or OFF
command, alarm A03 or A04 is triggered.
For more detailed information on the alarms,
please refer to chapter Alarms (Page 46).
s
5
1 … 900