Parameterization
9.3 Parameters
3KC ATC6300 transfer control device
Manual, 03/2018, L1V30535632002A-01
123
9.3.3
P03 - Password
The parameters for enabling / disabling the password are described below.
For entering the password, please refer to chapter Password protection (Page 36)
Note
Note the password
Please make a note of the new password that has been entered. Loss of this password
means that the device can no longer be parameterized. Please contact Technical Support if
you have lost the password.
P03
Password
Designation on ATC
display
Description
Default
Range
P03.01
Password Password Enabling the password protection
– If this parameter is set to OFF, no password protection is
enabled. This means that all parameters can be changed
on access to the ATC.
ON
OFF-ON
P03.02
User password
User level password
– Under this parameter and in connection with parameter
P03.01 a numeric code is set for the user level password.
(See chapter Password protection (Page 36))
1000
0-9999
P03.03
Advanced password Advanced level password
– Under this parameter and in connection with parameter
P03.01 a numerical code is set for the advanced level
password. (See chapter Password protection (Page 36))
2000
0-9999
P03.04
Remote password
Remote password
– Under this parameter a numerical code is set for the
password for remote access via MODBUS. This is inde-
pendent from the parameter P03.01.
3000
OFF/1-9999