Description
3.4 Parameterization
7KT multimeter
34
Manual, 08/2018, 2514284149-01
M08 Limit thresholds (LIMn, n = 1 to 4)
Note
This menu is divided into 4 sections for limit thresholds LIM 1 ... 4.
Unit
Default
Range
P08.n.01
Reference measure
–
OFF
OFF … (measures)
P08.n.02
Function
Max
•
Max
•
Min
•
Max + Min
P08.n.03
Upper threshold
0
−
9999 … +9999
P08.n.04
Multiplier
x1
x0.01 … x10k
P08.n.05
Delay
s
0
0.0 … 1000.0
P08.n.06
Lower threshold
–
−
9999 … +9999
P08.n.07
Multiplier
x1
x0.01 … x10k
P08.n.08
Delay
s
0
0.0 … 1000.0
P08.n.09
Status
–
OFF
•
OFF
•
ON
P08.n.10
Reset mode
P08.n.01
Defines the multimeter measurement to which the limit threshold applies.
P08.n.02
Defines the function of the limit threshold.
•
Max = LIMn active if the measurement exceeds P08. P08.n.03 is the reset
threshold.
•
Min = LIMn active if the measurement falls below P08. P08.n.06 is the reset
threshold.
•
Min + Max = LIMn active if the measurement exceeds P08.n.03 or falls
below P08.n.06.
P08.n.03,
P08.n.04
Defines the upper threshold resulting from the multiplication of the value
P08.n.03 by P08.n.04.
P08.n.05
Triggering delay for upper threshold.
P08.n.06,
P08.n.07,
P08.n.08
As above, but relating to the lower threshold.
P08.n.09
Permits inversion of the status of limit threshold LIMn.
P08.n.10
•
ON: You must manually save and reset the threshold value.
•
OFF: The threshold value is saved and reset automatically.
Summary of Contents for SENTRON 7KT PAC1600 Series
Page 2: ......
Page 10: ......
Page 14: ......
Page 42: ...Installation removal 4 3 Removal 7KT multimeter 40 Manual 08 2018 2514284149 01 4 3 Removal ...
Page 62: ......
Page 69: ...7KT multimeter Manual 08 2018 2514284149 01 67 Dimensional drawings 9 ...
Page 70: ......
Page 75: ......
Page 76: ......