Description
3.2 Measuring inputs
7KT multimeter
14
Manual, 08/2018, 2514284149-01
3.2
Measuring inputs
3.2.1
Current measurement
NOTICE
Device damage due to DC current
The device is not suitable for measuring DC current.
Only measure AC current with the device.
Design of the device
The devices are designed for a rated current of 1 A or 5 A for connecting standard current
transformers.
Ampacity of current measuring inputs
The current measuring inputs can be continuously loaded as follows:
●
With 1.2 A at a rated current of 1 A
●
With 6 A at a rated current of 5 A
3.2.2
Voltage measurement
NOTICE
Device damage due to DC current
The device is not suitable for measuring DC current.
Only measure AC current with the device.
Design of the device
The device is designed for:
●
Direct measurement on the grid
●
Nominal voltage 364 V/600 V