Appendix
A.2 Modbus register list
7KT PAC1200 multichannel current measuring system
68
System Manual, 11/2016, 2514374103-02
A.2
Modbus register list
Register overview
Start address
(decimal)
End address
(decimal)
Start address
(hexadecimal)
End address
(hexadecimal)
Size
Description
0
145
0x0000
0x0091
146
See 4.1 Internal,
immediate registers
512
791
0x0200
0x0317
280
See 4.2 Internal energy
registers (meters)
8192
8243
0x2000
0x02033
52
See 4-3 PnP
registers
40000
40177
0x9C40
0x9CF1
1788
See 4.4 SunSpec
registers
61440
65183
0xF000
0xFEFF
3840
See 4.5 Sensor registers
A.3
Internal registers
Internal, immediate registers
Start
address
(deci-
mal)
End
address
(deci-
mal)
Start
address
(hexa-
decimal)
End
address
(hexa-
decimal)
Size
R/W Func-
tion
codes
Type
Units
OBIS code
Description
0
1
0x0000
0x0001
2
RO 0x03
Unit 32 0.1 W
1-0:1.4.0*255
Active power
+
2
3
0x0002
0x0003
2
RO 0x03
Unit 32 0.1 W
1-0:2.4.0*255
Active power -
4
5
0x0004
0x0005
2
RO 0x03
Unit 32 0.1 var
1-0:3.4.0*255
Reactive
power +
6
7
0x0006
0x0007
2
RO 0x03
Unit 32 0.1 var
1-0:4.4.0*255
Reactive
power -
8
9
0x0008
0x0009
2
RO 0x03
—
—
—
(reserved)
10
11
0x000A 0x000B 2
RO 0x03
—
—
—
(reserved)
12
13
0x000C 0x000D 2
RO 0x03
—
—
—
(reserved)
14
15
0x000E 0x000F
2
RO 0x03
—
—
—
(reserved)
16
17
0x0010
0x0011
2
RO 0x03
Unit 32 0.1 VA
1-0:9.4.0*255
Apparent
power +