Description
3.4 Three-phase devices 80 A
7KT16 energy meter
Equipment Manual, 09/2020, 2514284147-04
33
3.4.4
Parameterization
3.4.4.1
Devices with RS 485 interface
You can transmit the measured values of the energy meters via the RS 485 interface.
The device functions as a standard Modbus slave.
The Modbus register table is provided in the appendix. You can find more information in
chapter Modbus address table for three-phase devices 80 A with Modbus interface (Page 91).
3.4.4.2
Devices with M-Bus interface
Devices with an M-Bus interface support 2 addressing paths:
•
Primary address from 1 to 250
•
Secondary address from 00000000 to 99999999
Baud rates from 300 to 38400 bps.
3.4.4.3
Setup parameter table for devices with RS 485 and M-Bus interface
For all variants
Code
Description
Default Range
P1-01
Password
0000
0000 … 9999
P1-02
Activate energy displays (export)
OFF
•
OFF
•
ON
P2-01
Measured variable for hour counter 1
limit
01 kW See Settable values for parameters
P2.01, P3.01, P4.01 (Page 40).
P2-02
Limit 1 ON
10.00
−
9999.99 … 9999.99
P2-03
Limit 1 OFF
5.00
−
9999.99 … 9999.99
P3-01
Measured variable for hour counter 2
limit
01 kW See Settable values for parameters
P2.01, P3.01, P4.01 (Page 40).
P3-02
Limit 2 ON
10.00
−
9999.99 … 9999.99
P3-03
Limit 2 OFF
5.00
−
9999.99 … 9999.99
P4-01
Measured variable for hour counter 3
limit
01 kW See Settable values for parameters
P2.01, P3.01, P4.01 (Page 40).
P4-02
Limit 3 ON
10.00
−
9999.99 … 9999.99
P4-03
Limit 3 OFF
5.00
−
9999.99 … 9999.99
P5-01
Function of input 1
OFF
•
OFF = Deactivated
•
ON = Activated
•
TAR = Tariff selection
•
CLr Part = Clear partial energy meter
•
CLr Hr = Clear hour counter
•
CLr dE = Clear max. demand values