Description
3.4 Three-phase devices 80 A
7KT16 energy meter
30
Equipment Manual, 09/2020, 2514284147-04
Setting parameters
1.
Press the "Next" key while
SETUP
is visible on the display.
The first parameter code P1-01 appears on the display.
2.
Use the "Increase" or "Decrease" key to move to the next parameters P-02, P-03, etc.
3.
When the display shows the code of the parameter to be changed, press "Next".
4.
When the code of the parameter that needs to be changed appears in the display, press
"Next".
The display shows the current value of the parameter.
5.
Change the value using the "Increase" or "Decrease" key.
6.
To define the default value, press the "Increase" and "Decrease" keys simultaneously.
7.
To return to parameter selection confirm with "Next".
8.
Press the "Increase" and "Decrease" keys simultaneously (> 1 s).
The parameters are saved. The system resumes normal operation.
3.4.2
Advanced functions
Procedure
1.
Press both keys "Increase" and "Decrease" simultaneously (> 5 s).
–
If password protection is activated,
PASS
appears on the display.
Proceed to point 2
(password entry).
–
If password protection is deactivated, (factory setting, default password = 0000),
proceed to point 6 (function selection).
2.
Release the keys.
0000
appears on the screen. The device is waiting for the password to be entered.
3.
Press "Increase" or "Decrease" to change the flashing digit.
4.
Press "Next" to select the next digit.
5.
After entering the password, press the "Next" key to confirm.
–
If the password is incorrect,
PASS Er
appears on the screen and the normal display
reappears.
–
If the password is correct, proceed to the next point.