Application Planning
3.2 Application and ambient conditions
Fail-safe operation of the Mobile Panel 277F IWLAN
44
Function Manual, 08/2008, 6AV6691-1FQ01-2AB0
Ambient conditions
Permitted range
Comments
SO
2
: < 0.5 vpm;
Relative humidity <
60 %, no condensation
Check: 10 cm
3
/m
3
; 10 days
Pollutant concentration
H
2
S: < 0.1 vpm;
Relative humidity <
60 %, no condensation
Check: 1 cm
3
/m
3
; 10 days
Climatic ambient conditions for the charging station
The following table shows the permitted climatic ambient conditions for use of the charging
station.
Ambient conditions
Permitted range
Comments
Temperature
•
Operation
•
Storage/transport
•
From 0 to 40 °C
•
From –20 to 60 °C
Relative humidity
5 to 85 %,
no condensation
Corresponds to relative humidity, load degree 2
in accordance with IEC 61131, part 2
Atmospheric pressure
1060 to 700 hPa
Corresponds to an elevation of –1,000 to
2,000 m
SO
2
: < 0.5 vpm;
Relative humidity <
60 %, no condensation
Check: 10 cm
3
/m
3
; 10 days
Pollutant concentration
H
2
S: < 0.1 vpm;
Relative humidity <
60 %, no condensation
Check: 1 cm
3
/m
3
; 10 days
Ambient climatic conditions for the transponder
The following table shows the permitted climatic ambient conditions for use of the
transponder:
Ambient conditions
Permitted range
Comments
Temperature
•
Operation
•
Storage/transport
•
0 to 50 °C
•
–20 to 60 °C
Relative humidity
5 to 85 %,
no condensation
Corresponds to relative humidity, load degree 2
in accordance with IEC 61131, part 2
Atmospheric pressure
1060 to 700 hPa
Corresponds to an elevation of –1,000 to
2,000 m
SO
2
: < 0.5 vpm;
Relative humidity <
60 %, no condensation
Check: 10 cm
3
/m
3
; 10 days
Pollutant concentration
H
2
S: < 0.1 vpm;
Relative humidity <
60 %, no condensation
Check: 1 cm
3
/m
3
; 10 days