background image

SIMADYN D
Digital Control System

Interface board  SB61

User Manual

Edition 05.95

DK-Nr. 283641

Summary of Contents for SB61

Page 1: ...SIMADYN D Digital Control System Interface board SB61 User Manual Edition 05 95 DK Nr 283641 ...

Page 2: ...ayment of damages All rights are reserved in the event of the grant of a patent or the registration of a utility model or design We have checked the contents of this Manual to ensure that they coincide with the described hardware and software However deviations cannot be completely ruled out so we cannot guarantee complete conformance However the information in this document is regularly checked a...

Page 3: ...l data 5 6 Connector assignment 6 6 1 Assignment of the binary outputs connector X1 6 6 2 Assignment of the power supply on the SIMADYN D side terminal blockX3 6 6 3 Assignment of the binary inputs terminal block X2 6 6 4 Assignment of the power supply on the process side terminal block X4 7 6 5 Assignment of test socket X5 7 7 Attachments 8 7 1 Block diagram 8 7 2 Dimension drawing 8 8 ECB instru...

Page 4: ...Warning information Edition 05 95 Siemens AG Dk Nr 283641 SIMADYN D Hardware User Manual ...

Page 5: ...t or relationship The sales contract contains the entire obligation of Siemens The warranty contained in the contract between the parties is the sole warranty of Siemens Any statements contained herein do not create new warranties nor modify the existing warranty Warning information W A R N I N G Electrical equipment has components which are at dangerous voltage levels If these instructions are no...

Page 6: ... labels Warning indicates death severe personal injury or property damage can result if proper precautions are not taken CAUTION For the purpose of this User Manual and product labels Caution indicates that minor personal injury or material damage can result if proper precautions are not taken NOTE For the purpose of this User Manual Note indicates information about the product or the respective p...

Page 7: ...ons SIMADYN D side P24V 48V M24V 48V 1 11 51 3 2 X2 X11 Electrical isolation SB61 a Version 1 inputs with electrical isolation between each other b Version 2 inputs with common reference potential Plant side SIMADYN D side Electrical isolation X2 1 11 SB61 X11 X4 M24V 48V P24V 48V 51 3 2 4 1 2P 2M Plant side When supplied the board corresponds to version 2 i e terminal pair X11 to X18 is each equi...

Page 8: ... socket with output 2P and 2M Short circuit plug connector Ribbon cable connector 8 pins for binary outputs 2 pins for 1P 1M Display LEDs Green 1P 1M supply available on the SIMADYN D side Red 1P 1M supply short circuited fault Yellow Binary signals 1 to 8 active Optocoupler for electrically isolating input and output Labels or print to identify the board LEDs and the test socket 4 Application inf...

Page 9: ...IONS 118mm 135mm 42mm WEIGHT approx 320g Supply voltage Vv DC voltage SIMADYN D side System side at 24V System side at 48V Nominal value Permissible range Briefly 24V 20V to 30V 1 5 Vrated Duration 0 5s 24V 20V to 30V 1 5 Vrated Duration 0 5s 48V 40V to 60V 1 5 Vrated Duration 0 5s Current drain nominal value 90mA 50mA 50mA 8 inputs Input voltage for 1 signal for 0 signal Input current 1 signal 13...

Page 10: ...Assignment of the binary inputs terminal block X2 Terminal Version 1 Version 2 Channel number 1 2 3 4 5 6 7 8 24V input 24V input 24V input 24V input 24V input 24V input 24V input 24V input Channel 1 Channel 2 Channel 3 Channel 4 Channel 5 Channel 6 Channel 7 Channel 8 11 12 13 14 15 16 17 18 48V input 48V input 48V input 48V input 48V input 48V input 48V input 48V input Channel 1 Channel 2 Channe...

Page 11: ...he power supply on the process side terminal block X4 Terminal Designation 2P 2M P24 48 24V 48V supply on the process side M24 48 24V 48V supply on the process side 6 5 Assignment of test socket X5 Socket Designation G Ground M24 48 24V 48V supply from the process side P24 48 24V 48V supply from the process side ...

Page 12: ...tachments 8 Edition 05 95 Siemens AG Dk Nr 283641 SIMADYN D Hardware User Manual 7 Attachments 7 1 Block diagram SIMADYN D SB61 6DD1681 0FB0 7 2 Dimension drawing Dimension drawing 3SE 465 681 9041 30 MB ...

Page 13: ...h highly insulating materials e g plastic foils insulated desktops articles of clothing manufactured from man made fibers Boards must only be placed on conductive surfaces When soldering the soldering iron tip must be grounded Boards and components should only be stored and transported in conductive packaging e g metalized plastic boxes metal containers If the packing material is not conductive th...

Page 14: ...ECB instructions 10 Edition 05 95 Siemens AG Dk Nr 283641 SIMADYN D Hardware User Manual ...

Page 15: ...CB instructions Siemens AG Dk Nr 283641 Edition 05 95 11 SIMADYN D Hardware User Manual Drives and Standard Products Motors and Drives Systems Group Postfach 3269 D 91050 Erlangen System Based Technology ...

Reviews: