38
RoHS
Section 5.1.6
RoHS
This device is declared by Siemens Canada Ltd to meet the requirements of the following RoHS (Restriction of
Hazardous Substances) directives for the restricted use of certain hazardous substances in electrical and electronic
equipment:
•
China RoHS 2
Administrative Measure on the Control of Pollution Caused by Electronic Information Products
A copy of the Material Declaration is available online at
https://support.industry.siemens.com/cs/ww/en/
Section 5.2
EMC and Environmental Type Tests
The RUGGEDCOM WIN7014 has passed the following Electromagnetic Compatibility (EMC) and environmental
tests.
EMC Type Test for IEC 61850-3
Standard
Method
Description
Test Levels
Climatic Environmental Conditions
IEC 60068-2-1
IEC 61850-3 (5.2)
Low Temperature (Operational)
-40 °C (-40 °F), 16 Hour Dwell
IEC 60068-2-2
IEC 61850-3 (5.2)
High Temperature (Operational)
-65 °C (-149 °F), 16 Hour Dwell
IEC 60068-2-1
IEC 61850-3 (5.2)
Low Temperature (Storage)
-40 °C (-40 °F), 16 Hour Dwell
IEC 60068-2-2
IEC 61850-3 (5.2)
High Temperature (Storage)
-65 °C (-149 °F), 16 Hour Dwell
IEC 60068-2-30
IEEE 61850-3 (5.2)
Humidity (Operational)
95% at 55 °C (131 °F) for 96 Hours
IEC 60068-2-30
IEEE 61850-3 (5.2)
Humidity (Storage)
95% at 55 °C (131 °F) for 96 Hours
Mechanical Environmental Conditions
IEC 60068-2-27
IEC 61850-3 (5.5)
Shock
30 g (965 ft/s
2
)
IEC 60068-2-6
IEC 61850-3 (5.5)
Vibration
2 g (32 ft/s
2
), 10-150 Hz per Axis
EMC
IEC 61000-4-6
IEC 61850-3
(5.7.1.1)
Conducted Immunity
10 Vrms
IEC 61000-4-5
IEC 61850-3
(5.7.1.2)
Surges Immunity
4 kV L-G
IEC 61000-4-12
IEC 61850-3
(5.7.1.3)
Oscillatory Surge
2.5 kV
IEC 61000-4-4
IEC 61850-3
(5.7.1.4)
Electrical Fast Transients Immunity
4 kV
IEC 61000-4-3
IEC 61850-3 (5.7.2)
Radiated Susceptibility Immunity
20 V/m