Certification
6.2 EMC and Environmental Type Tests
Test
Description
Test Levels
Severity
Levels
IEC 61000-4-17
Ripple on DC
Power Supply
DC Power Ports
10%
3
IEC 61000-4-29
Voltage Dips
and Interrupts
DC Power Ports
30% for 0.1 s
60% for 0.1 s
100% for 0.05 s
Signal ports
2 kV (Failsafe Relay output)
Dielectric Strength
DC Power Ports
2 kV
Signal ports
5 kV (Failsafe Relay output)
IEC 60255-5
HV Impulse
DC Power Ports
5 kV
Siemens-specified severity levels
EMC Immunity Type Tests for IEEE 1613
Note
The RUGGEDCOM RX1512 meets Class 2 requirements for an all-fiber configuration
and Class 1 requirements for copper ports. Class 1 allows for temporary communica-
tion loss, while Class 2 requires error-free and interrupted communications.
Description
Test Levels
Signal ports
5 kV (Failsafe Relay Output)
HV Impulse
DC Power Ports
5 kV
Signal ports
2 kV
Dielectric Strength
DC Power Ports
2 kV
Signal ports
± 4 kV @ 2.5 kHz
DC Power Ports
Fast Transient
Earth ground ports
± 4 kV
Signal ports
2.5 kV common mode @1MHz
Oscillatory
DC Power Ports
2.5 kV common
1 kV differential mode @ 1 MHz
Radiated RFI
Enclosure ports
35 V/m
Enclosure Contact
± 8 kV
ESD
Enclosure Air
± 15 kV
Environmental Type Tests
Test
Description
Test Levels
Severi-
ty Levels
IEC 60068-2-1
Cold Temperature
Test Ad
-40 °C (-40 °F), 16 Hours
IEC 60068-2-2
Dry Heat
Test Bd
85 °C (185 °F), 16 Hours
IEC 60068-2-30
Humidity (Damp
Heat, Cyclic)
Test Db
95% (non-condensing),
55 °C (131 °F), 6 cycles
IEC 60255-21-1
Vibration
2 g @ 10-150 Hz
Class 2
RUGGEDCOM RX1512
Installation Manual, 07/2019, C79000-G8976-1057
41