RUGGEDCOM RX1100P
Installation Guide
Chapter 4
Technical Specifications
Serial Port Specifications
35
NOTE
• All optical power numbers are listed as dBm averages. To convert from average to peak add 3 dBm.
To convert from peak to average, subtract 3 dBm.
• Maximum segment length is greatly dependent on factors such as fiber quality, and the number
of patches and splices. Consult a Siemens sales associate when determining maximum segment
distances.
Mode
Connector
Type
Cable
Type (μm)
Tx λ (typ.)
(nm)
Tx min.
(dBm)
Tx max.
(dBm)
Rx
Sensitivity
(dBm)
Rx
Saturation
(dBm)
Distance
(typ.) (km)
Power
Budget
(dB)
62.5/125
-19
12
MM
ST
50/125
1300
-22.5
-14
-31
-14
2
8.5
62.5/125
-19
12
MM
SC
50/125
1300
-22.5
-14
-31
-14
2
8.5
MM
MTRJ
62.5/125
1300
-19
-14
-31
-14
2
12
SM
ST
9/125
1300
-15
-8
-32
-3
20
17
SM
SC
9/125
1300
-15
-8
-31
-7
20
16
SM
LC
9/125
1300
-15
-8
-34
-7
20
19
SM
SC
9/125
1300
-5
0
-34
-3
50
29
SM
LC
9/125
1300
-5
0
-35
3
50
30
SM
SC
9/125
1300
0
5
-37
0
90
37
SM
LC
9/125
1300
0
5
-37
0
90
37
MM
LC
50/125
1300
-22.5
-14
-31
-14
2
8.5
Section 4.6
Serial Port Specifications
Baud Rate
Connector
Isolation
300 to 230 kbps
RJ45
2.5 kV
Section 4.7
IRIG-B Output Specifications
Parameter
Typical Value
Output Current (IS)
40 mA total between two output ports
Output Voltage (VS)
5 Vp-p
Output Impedance (RS)
25 Ω