RUGGEDCOM RS969
Installation Guide
Chapter 7
Certification
EMC and Environmental Type Tests
43
Test
Description
High Temperature Method 501.4 Procedure II Operational
Low Temperature Method 502.4 Procedure I Storage
Low Temperature Method 502.4 Procedure II Operational
Temperature Shock Method 503.4 Procedure I Storage
Acceleration Method 513.5 Procedure II
Salt Fog Method 509.4 Procedure I
Vibration Method 514.5
MIL-STD 901D
High Impact Shock Test
MIL-STD-1275B
Power Quality
MIL-STD-1399
DC Magnetic Field Testing Section 070 Part 1
Section 7.3
EMC and Environmental Type Tests
The RUGGEDCOM RS969 has passed the following EMC and environmental tests.
IEC 61850-3 Type Tests
Test
Description
Test Levels
Severity
Levels
Enclosure Contact
± 8 kV
4
IEC 61000-4-2
ESD
Enclosure Air
± 15 kV
4
IEC 61000-4-3
Radiated RFI
Enclosure ports
20 V/m
x
Signal ports
± 4 kV @ 2.5 kHz
x
DC Power ports
± 4 kV
4
AC Power ports
± 4 kV
4
IEC 61000-4-4
Burst (Fast Transient)
Earth ground ports
± 4 kV
4
Signal ports
± 4 kV line-to-earth, ± 2 kV line-to-line
4
DC Power ports
± 2 kV line-to-earth, ± 1 kV line-to-line
3
IEC 61000-4-5
Surge
AC Power ports
± 4 kV line-to-earth, ± 2 kV line-to-line
4
Signal ports
10V
3
DC Power ports
10 V
3
AC Power ports
10 V
3
IEC 61000-4-6
Induced
(Conducted) RFI
Earth ground ports
10 V
3
IEC 61000-4-8
Magnetic Field
Enclosure ports
40 A/m continuous, 1000 A/m for 1 s
—
Summary of Contents for RUGGEDCOM RS969
Page 4: ...RUGGEDCOM RS969 Installation Guide iv ...
Page 10: ...Preface RUGGEDCOM RS969 Installation Guide x Customer Support ...
Page 18: ...Chapter 1 Introduction RUGGEDCOM RS969 Installation Guide 8 Decommissioning and Disposal ...
Page 40: ...Chapter 5 Technical Specifications RUGGEDCOM RS969 Installation Guide 30 Dimension Drawings ...