Installing Device
2.2.1 Connecting AC Power
• For 100-240 VAC rated equipment, an appropriately rated AC circuit breaker
must be installed.
• For 88-300 VDC rated equipment, an appropriately rated DC circuit breaker must
be installed.
• Use minimum #16 gage wiring when connecting terminal blocks.
• A circuit breaker is not required for 12, 24 or 48 VDC rated power supplies.
• It is recommended to provide a separate circuit breaker for each power supply
module.
• Equipment must be installed according to applicable local wiring codes and
standards.
2.2.1
Connecting AC Power
To connect a high AC power supply to the device, do the following:
NOTICE
Electrical hazard – risk of damage to equipment
Do not connect AC power cables to a DC power supply terminal block. Damage to
the power supply may occur.
NOTICE
Electrical hazard – risk of damage to equipment
Before testing the dielectric strength (HIPOT) in the field, remove the braided
ground cable connected to the surge ground terminal and chassis ground. This cable
connects transient suppression circuitry to chassis ground and must be removed in
order to avoid damage to transient suppression circuitry during testing.
RUGGEDCOM RS1600
Installation Manual, 01/2021, C79000-G8976-1013-03