Central control unit RMB795B
CE1P3122en
Building Technologies
Inputs
18.01.2012
No.
Text
Effect
101…
224
[N.X1] sensor error..
[RMZ787(2).X4]
sensor fault
Non urgent message; must not be
acknowledged.
For each Synco system, only one outside temperature can be sent within the same
zone, i.e. only one outside temperature master.
An error message occurs if multiple devices in the same zone send their outside
temperatures: ">1 outside temperature sensor"
The message is delivered by the devices that send outside temperature signals to
and receive them from the same zone.
No.
Text
Effect
11 >1
outside
temperature sensor
Urgent message; must be acknowledged.
If the RMB795B central control unit expects an outside temperature from the bus
and that outside temperature is not communicated, the following fault status
message will be delivered: "Outside temp sensor error".
No.
Text
Effect
10
Outside temp sensor
error
Non urgent message; must not be
acknowledged.
If other outside temperature signals are available on the bus, any of them are used
randomly.
7.6
Texts
Each input can be assigned plant-specific text with a maximum length of
20 characters.
Such texts are displayed locally in place of standard text (e.g. N.X1).
Main menu > Commissioning > Settings > …
or
Main menu > Settings > Inputs > ...X...
Operating line
Range
Factory setting
N.X1
Max. 20 characters.
N.X1
N.X2
Max. 20 characters.
N.X2
N.X3
Max. 20 characters.
N.X3
N.X4
Max. 20 characters.
N.X4
N.X5
Max. 20 characters.
N.X5
N.X6
Max. 20 characters.
N.X6
RMZ785.X1
Max. 20 characters.
RMZ785.X1
RMZ785.X2
Max. 20 characters.
RMZ785.X2
RMZ785.X3
Max. 20 characters.
RMZ785.X3
RMZ785.X4
Max. 20 characters.
RMZ785.X4
RMZ785.X5
Max. 20 characters.
RMZ785.X5
RMZ785.X6
Max. 20 characters.
RMZ785.X6
RMZ785.X7
Max. 20 characters.
RMZ785.X7
RMZ785.X8
Max. 20 characters.
RMZ785.X8
RMZ787(1).X1
Max. 20 characters.
RMZ787(1).X1
Fault status messages
Only 1 outside
temperature allowed
per zone
Fault status message
Outside temperature
via bus available?
Fault status message
Plant-specific text
Setting values