Siemens
Central control unit RMB795B
CE1P3122en
Building Technologies
Inputs
18.01.2012
7.2.6
Multiple use of sensors
Not all sensor signals can be routed via bus to another device.
For this reason, function "Multiple use of sensors" allows for wiring a passive signal
at an input terminal directly to a Y-output and provide it as a DC 0…10 V signal.
The signal can then be fed to other devices.
Main menu > Commissioning > Extra configuration > Sensor multiple use
Operating line
Adjustable values / remarks
Signal Y N.X1…
Activate function by assigning an input terminal to the
output terminal.
Conversion of a Ni 1000 or Pt 1000 signal to a DC 0...10 V signal is made via
parameter setting "Value low" or "Value high".
See Sec. 7.5.2 "Outside temperature at terminal".
7.3
Digital inputs (Xx)
7.3.1
Use and activation
Control function signals can be connected to the digital inputs.
The inputs can be activated as described under Sec. 7.1.2 "Activate function".
7.3.2
Normally closed
Normally closed can be defaulted for each digital input:
Main menu > Commissioning > Settings > ....
or
Main menu > Settings > Inputs > ...X...
Operating line
Range
Factory setting
Normally closed
Open, closed.
Open.
7.3.3
Texts for logical states 0 and 1
Each digital input can be assigned the logic states 0 and 1 and one free text (e.g.
on/off, full/empty, etc.). A default text is displayed on the impacted input.
Main menu > Commissioning > Settings > …
or
Main menu > Settings > Inputs > ...X...
Operating line
Range
Factory setting
Text for: Logic 0
Max. 20 characters.
0
Text for: Logic 1
Max. 20 characters.
1
Problem and solution
Configuration
Setting values
Use
Activation
Setting values
Setting values