Electrical connections
18.01.2012
18.2 Connection terminals
18.2.1 Central control unit RMB795B
G
X2 M G1 X3 M X4 M G1 X5 M
X6 M G1
Q33
Q53
Q34
Q54
M
X1
G0 G1 Y1 G0 G1 Y2 G0
CE
CE
31
21
G
01
Q12
Q14
Q11
Q23
Q24
G, G0
AC 24 V rated voltage
G1
AC 24 V power supply for active sensors, signal sources or limiters
M
Measuring neutral for signal input
G0
System neutral for signal output
X1...X6
Universal signal inputs for
LG-Ni 1000, 2x LG-Ni 1000 (averaging), T1, Pt 1000, DC 0...10 V,
contact sensing (potential-free)
Y1...Y2
Control or status outputs, analog DC 0...10 V
Q1...
Potential-free relay outputs (changeover) for AC 24...230 V
Q2...
Potential-free relay outputs (N.O.) for AC 24...230 V
Q3...
Potential-free relay outputs (N.O.) for AC 24...230 V
Q5...
Potential-free relay outputs (N.O.) for AC 24...230 V
CE
+
KNX bus data line, positive
CE
−
KNX bus data line, negative
18.2.2 Universal modules RMZ785
X3 M
X4 M G1
X2 M G1
M
X1
31
4
6G
03
X7 M
X8 M
X6 M G1
M
X5
RMZ785
M
Measuring neutral for signal input
X1...X8
Universal signal inputs for:
LG-Ni 1000, 2x LG-Ni 1000 (averaging), T1, Pt 1000, DC 0...10 V,
contact sensing (potential-free)
18.2.3 Universal module RMZ787
X3 M
X4 M G1
Q13
Q23
Q14
Q24
X2 M G1
M
X1
Q34
Q33
31
46
G
01
Q52
Q54
Q51
RMZ787
M
Measuring neutral for signal input
G1
Power supply AC 24 V for connected active devices.
X1...X4
Universal signal inputs for:
LG-Ni 1000, 2x LG-Ni 1000 (averaging), T1, Pt 1000, DC 0...10 V,
contact sensing (potential-free)
Q1...
Potential-free relay outputs (N.O.) for AC 24...230 V
Q2...
Potential-free relay outputs (N.O.) for AC 24...230 V
Q3...
Potential-free relay outputs (N.O.) for AC 24...230 V
Q5...
Potential-free relay outputs (changeover) for AC 24...230 V
RMB795B
Key
RMZ785
Key
RMZ787
Key