Help in case of faults
18.01.2012
17
Help in case of faults
17.1 Error/fault code list
The following list contains all codes and assigned texts that appear in the event of
fault.
Code
no.
Cause of fault
Effect
10
Outside temp sensor error
see 7.5 "Outside temperature"
11
>1 outside temperature sensor
Ditto
12
Outs sensor simulation active
Ditto
101
...224
[N.X1] sensor error
...
[RMZ787(2).X4] sensor fault
See 7.2 "Analog inputs (Xx)"
See 7.5 "Outside temperature"
3880
...
3889
Smoke Extraction room group 1
...
Smoke Extraction room group 10
See 17.2 "Troubleshooting faults".
3890
...
3899
Fire alarm off room group 1
...
Fire alarm off room group 10
Ditto
3931
Simulation VAV supply air
See Sec. 12 "Volume flow
balancing VAV"
3932
Simulation VAV extract air
Ditto
4501
Room temperature > Limit val.
and R'grp 1
see 8.6 "Temperature supervision"
... ...
Ditto
4591
Room temperature > Limit val.
and R'grp 10
Ditto
4502
Room temperature > Limit val. or
R'grp 1
Ditto
...
Ditto
4592
Room temperature > Limit val. or
R'grp 10
Ditto
4503
Device supervision room grp 1
See 16 "Device supervision"
...
Ditto
4593
Device supervision room grp 10
Ditto
4920
RXB/RXL room temperature frost
Triggered by a RXB/RXL room
controller. No impact on central
control unit RMB795B. It only
displays the fault.
4930
RXB/RXL room temperature
condensation
Ditto
4940
RXB/RXL outside air frost
Ditto
4950
RXB/RXL El air heater overtemp.
Ditto
4960
RXB/RXL general fault
Ditto
5000
No bus power supply
See 13 "Communication".
5001
System time failure
See 6.1 "Time of day and date"
5002
> 1 clock time master
Ditto
5003
Invalid time of day
Ditto
5102
>1 Time switch in room group 1
Cause and effect