Siemens
Central control unit RMB795B
CE1P3122en
Building Technologies
Device supervision
18.01.2012
The "Create" command is used to generate a complete device list. For that, a
search is made on the KNX bus aimed at finding individual room controllers that
have the same "Geographical zone (apartment) When the RMB795B central
control unit receives a reply from an individual room controller, it is entered on the
device list.
The search process takes several minutes, depending on the number of activated
room groups. During the search process, the sandglass symbol
appears on the
"Device list" line.
When the search process is finished, a tick will appear
.
Now, the number of identified devices is valid.
If the number of devices are not identical with the number given in the planning
documentation, the connection to the individual room controllers is to be checked.
The "Update" command is used to search the plant for devices that have not yet
been detected.
This command is to be executed when devices have been added to the plant at a
later point in time, for example.
The "Delete" command deletes the device list. Supervision does not occur when
the list is empty and the number of identified devices is 0 accordingly.
16.4 Read device list
The list of assigned and supervised devices per room group can be read:
Main menu > Room group 1…10 > Device supervision >
Operating line
Adjustable values / remarks
Number devices
current
Number of RXB/RXL room controllers and
RDF/RDG/RDU room thermostats assigned to the
room group.
Zone (Apart.Room)
Zone address (apartment.room) of the supervised
room controllers, room thermostats.
The list displayed provides the following information:
•
Number of individual room controllers assigned to this room group
•
and their geographical zone address on the display (apartment.room).
Device supervision
Number dev current 14
Zone (apart.room) 2.15 ?
Zone (apart.room) 2.1
Zone (apart.room) 2.2
Symbol
Meaning
Examples
(Without) Connection to room controller, room
thermostat is ok.
Zone (Apart.Room) 2.1
?
Connection to room controller, room
thermostat is interrupted.
Zone (Apart.Room)
2.15 ?
Based on the information of "Zone (apart.room)" and the plant diagram, the
relevant individual room controller can be clearly identified.
If no devices are assigned to the selected room group, the value of "Number dev
current" is "0" and under "Zone (apart.room)", symbol " -.- " appears everywhere.
Command "Create"
Search process
Command "Update"
Command "Delete"
Settings
Display
Notes