Parameter:
Phase Rotation
•
Default setting:
ABC
This setting can be used when the device is used with primary systems having reverse phase rotation.
This allows the device functionality to operate correctly on these systems.
Settings Menu
Configuration > System Config
Parameter
Range
Default Setting
CT1/2/3 Nominal
1 A/5 A
1 A
CT1/2/3 Ratio Prim
000000 to 999999
2000 A
CT1/2/3 Ratio Sec
0.2 to 7
1
CT5/6/7 Nominal
1 A/5 A
1 A
CT5/6/7 Ratio Prim
000000 to 999999
2000 A
CT5/6/7 Ratio Sec
0.2 to 7
1
CT9/10/11 Nominal
1
1 A/5 A
1 A
CT9/10/11 Ratio Prim
1
000000 to 999999
2000 A
CT9/10/11 Ratio Sec
1
0.2 to 7
1
CT4 Nominal
1 A/5 A
1 A
CT4 Ratio Prim
000000 to 999999
2000 A
CT4 Ratio Sec
0.2 to 7
1
CT8 Nominal
1 A/5 A
1 A
CT8 Ratio Prim
000000 to 999999
2000 A
CT8 Ratio Sec
0.2 to 7
1
CT12 Nominal
1
1 A/5 A
1 A
CT12 Ratio Prim
1
000000 to 999999
2000 A
CT12 Ratio Sec
1
0.2 to 7
1
VT1/2/3 Ratio Prim
2
000000 to 999999
132000 V
VT1/2/3 Ratio Sec
2
40 V to 160 V
110 V
VT1/2/3 Nominal
2
40 V to 160 V
63.5 V
VT1/2/3 Trim Magnitude
2
0 V to 20 V
0 V
VT1/2/3 Trim Angle
2
-45° to +45°
0°
VT1/2/3 Config
2
Van, Vbn, Vcn
Vab, Vbc, 3V0
Va, Vb, Vc
Van, Vbn, Vcn
VT4 Nominal
2
40 V to 160 V
63.5 V
VT4 Ratio Prim
2
000000 to 999999
132000 V
VT4 Ratio Sec
2
40 V to 160 V
110 V
VT4 Trim Magnitude
2
0 V to 20 V
0 V
VT4 Trim Angle
2
-45° to +45°
0°
Phase Rotation
2
ABC
3.3.4
1
7SR543 devices only
2
Devices with VT inputs only
Device Functionality
3.3 CT and VT Inputs
64
Reyrolle 7SR5, Transformer Protection Device, Device Manual
C53000-G7040-C015-1, Edition 11.2019