81HB5 Overfluxing Detection – 5th Harmonic
Reference
Parameter
Value
Bias
Cross, Phase, Sum
I
set
5
th
harmonic current content setting
0.1 to 0.5 ⋅ I, Δ 0.01
I
Applied current (for operate time)
0 to 2 ⋅ I
set
(switched)
Operate and Reset Level
Attribute
Value
I
op
Operate level
100 % I
set
± 5 % or ± 0.01 I
rated
Reset level
< 95 % I
op
Repeatability
± 1 %
Variation IEC
60255-1
-10 °C to +55 °C
≤ 5 %
f
rated
± 5 %
≤ 5 %
10.30
Technical Data
10.30 81HB5 Overfluxing Detection – 5th Harmonic
Reyrolle 7SR5, Transformer Protection Device, Device Manual
497
C53000-G7040-C015-1, Edition 11.2019