67GS Directional Sensitive Earth Fault – Measured
Reference
Parameter
Value
θ
set
Characteristic angle setting
-95° to +95°
Vmin
set
Minimum voltage setting
0.33 to 67 V, Δ 0.5 V
I
Applied current (for operate time)
0.1 ⋅ I
rated
1 ⋅ I
rated
V
Applied voltage (for operate time)
0.1 ⋅ V
rated
1 ⋅ V
rated
Compensated network
Enabled / disabled
Wattmetric
Enabled / disabled
Wattmetric power
0.05 to 20 ⋅ I
rated
⋅ W, Δ 0.05
I
res
select
I
res
, I
res
real
Operate Angle
Attribute
Value
θ
op
Characteristic angle (I with respect to V)
θ
set
, ± 5°
Operating angle
Forward
θ
set
- 85° ± 5° to θ
set
+ 85° ± 5°
Reverse
(θ
set
- 180°) - 85° ± 5° to (θ
set
- 180°) + 85 ° ± 5°
Variation in charac-
teristic angle
-10 °C to +55 °C
± 5 °C
f
rated
± 5 %
± 5 °C
Operate Threshold
Attribute
Value
Minimum operating voltage
> 1 V ± 0.25 V
Operate and Reset Time
Attribute
Value
t
op
Operate time
Typically 32 ms
< 40 ms at characteristic angle + 50/51 element operate time
t
reset
Reset time
Typically < 65 ms at characteristic angle
10.26
Technical Data
10.26 67GS Directional Sensitive Earth Fault – Measured
Reyrolle 7SR5, Transformer Protection Device, Device Manual
493
C53000-G7040-C015-1, Edition 11.2019