59Vx Overvoltage Protection – Vx
Reference
Parameter
Value
V
set
Setting
5 to 199.5, 200 V
V
Applied voltage (for operate time)
0 to 1.1 ⋅ V
set
(switched)
0 to 2 ⋅ V
set
(switched)
Hysteresis
Hysteresis
0 to 80 %
t
delay
Delay setting
0 to 20 s, Δ 0.01 s
20 to 100 s, Δ 0.1 s
100 to 1000 s, Δ 1 s
1000 to 10000 s, Δ 10 s
1000 to 14400 s, Δ 100 s
Operate and Reset Level
Attribute
Value
V
op
Operate level
V
set
: ± 2 % or ± 0.5 V
Reset level
V
op
- hysteresis ± 2 % or 0.5 V
Repeatability
± 1 %
Variation IEC
60255-1
-10 °C to +55 °C
≤ 5 %
f
rated
± 5 %
≤ 5 %
Operate and Reset Time
Attribute
Value
t
basic
Element basic operate time
1.1 ⋅ V
set
: 73 ms ± 10 ms
2 ⋅ V
set
: 63 ms ± 10 ms
t
op
Operate time following delay
t
basic
+ t
delay
± 1 % or ± 10 ms
Repeatability
± 1 % or ± 10 ms
Overshoot time
Disengaging time
< 80 ms
10.21
Technical Data
10.21 59Vx Overvoltage Protection – Vx
488
Reyrolle 7SR5, Transformer Protection Device, Device Manual
C53000-G7040-C015-1, Edition 11.2019