50BF Circuit-Breaker Failure Protection – 3 Pole
50BF Circuit‑Breaker Failure Protection – 3 Pole
Reference
Parameter
Value
I
set
Setting
0.050 to 2 ⋅ I
rated
t
delay1
Stage 1 delay setting
20 to 60000 ms
t
delay2
Stage 2 delay setting
20 to 60000 ms
Operate and Reset Level
Attribute
Value
I
op
Operate level
I
set
, ± 5 % or ± 1 % I
rated
I
reset
Reset level
< 100 % I
op
± 5 % or ± 1 % I
rated
Repeatability
± 1 %
Variation IEC
60255-1
-10 °C to +55 °C
≤ 5 %
f
rated
± 5 %
≤ 5 %
Operate and Reset Time
Attribute
Value
t
basic
Element basic operate time
< 20 ms
t
op
Stage 1
t
delay1
, ± 1 % or ± 20 ms
Stage 2
t
delay2
, ± 1 % or ± 20 ms
Repeatability
± 1 % or ± 20 ms
Overshoot
< 2 ⋅ 20 ms
Disengaging time
< 30 ms
Circuit‑Breaker Supervision
Position supervision via circuit‑breaker auxiliary contacts
For 3 pole CB tripping
1 input each for make contact and break contact
i
i
NOTE
The circuit‑breaker failure protection can also work without the circuit‑breaker auxiliary contacts stated.
Auxiliary contacts are required for circuit‑breaker failure protection in cases where the current flow is
absent or too low for tripping (for example with a transformer or a Buchholz protection).
Times
Pickup time, in the case of an internal start
Pickup time, in the case of an external start
< 1 ms
< 5 ms
Dropout time for unbalancing operating mode
Approx. 2 ms
Typical dropout time
< 15 ms
Dropout time via circuit‑breaker auxiliary contact
criterion
< 5 ms
10.13
10.13.1
Technical Data
10.13 50BF Circuit-Breaker Failure Protection – 3 Pole