Logic of the Function
[lo_7SR5_37logicdiagram, 1, en_US]
Figure 5-6
Logic Diagram: 37 Undercurrent Protection – Phase
Application and Setting Notes
Parameter:
37 Common > UC Guard Setting
•
Default setting: 0.1 x I
n
(0.1 ⋅ I
rated
)
Current elements can be blocked if all phase currents fall below setting.
Parameter:
Element
•
Default setting:
Disabled
This setting is used to allow the element to be switched on and off if it is not required. A separate setting
is provided for each element. This setting can be used to select the number of elements required.