IEC 61850 Functional Information Mapping
A27PTUV*.Mod
Information
27 Undervoltage Enabled (Function Config)
0
1
1
x
x
Inhibit 27-n
x
0
1
x
x
27-n Enabled
1
1
1
0
x
27-n Operation: Under
1
1
1
x
0
A27PTUV*.Mod.stVal
2
1
2
5
5
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
Irrelevant: x
IEC 61850 Value
OK: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
A27PTUV*.Health
Information
Device Healthy
0
1
A27PTUV*.Health.stVal
3
1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value
OK: 1
WARNING: 2
ALARM: 3
A27PTUV*.Op
Information
27-n Operated
0
1
A27PTUV*.Op.general
0
1
Device Annunciation ON/TRUE: 1
OFF/FALSE: 0
IEC 61850 Value
TRUE: 1
FALSE: 0
A27PTUV*.Str
Information
27-n Pickup
0
1
A27PTUV*.Str.general
0
1
5.3.6
Protection and Automation Functions
5.3 27 Undervoltage Protection – 3-Phase
Reyrolle 7SR5, Transformer Protection Device, Device Manual
163
C53000-G7040-C015-1, Edition 11.2019