Element
Setting Values
27-1
U/V Guarded
Yes
27-1
VTS Inhibit
Yes
27-1
O/P Phases
All
27-2
Element
Enabled
27-2
Setting
77 V
27-2
Hysteresis
3 %
27-2
Delay
1 s
27-2
UV Guarded
Yes
27-2
VTS Inhibit
Yes
27-2
O/P Phases
All
Settings Menu
Functions > Function Config
Parameter
Range
Settings
Default Gn1
Gn2
Gn3
Gn4
27 Undervoltage
Enabled
Disabled
Disabled
Functions > Protection > 27 > Gn 27 Common
Parameter
Range
Settings
Default Gn1
Gn2
Gn3
Gn4
Input Selection
Ph-Ph
Ph-N
Ph-Ph
UV Guard Setting
1 to 200 V, Δ 0.5 V
5 V
Functions > Protection > 27 > Gn 27-n
Parameter
Range
Settings
Default Gn1
Gn2
Gn3
Gn4
Element
Enabled
Disabled
Disabled
Setting
5 to 200 V, Δ 0.5 V
80 V
Hysteresis
0 to 80 %, Δ 0.1 %
3 %
Delay
0 to 20 s Δ 0.01 s
20 to 100 s Δ 0.1 s
100 to 1000 s Δ 1 s
1000 to 10000 s Δ 10 s
10000 to 14400 s Δ 100 s
0.1 s
VTS Inhibit
No
Yes
No
UV Guard Inhibit
No
Yes
Yes
Pickup Option
Any
All
Any
5.3.5
Protection and Automation Functions
5.3 27 Undervoltage Protection – 3-Phase
162
Reyrolle 7SR5, Transformer Protection Device, Device Manual
C53000-G7040-C015-1, Edition 11.2019