Installation Instructions 

Document No. 129-116  

September 24, 2009

 

 

TH 192 Pneumatic Room Thermostat 
Retrostat Kits 

 

 

Item Number 129-116, Rev. FA

 

Page 1 of 12 

Product Description 

The TH 192 Pneumatic Room Thermostat Retrostat 
kits convert most existing pneumatic room 
thermostats to a Powers™ Controls TH 192 direct or 
reverse acting, two-pipe, single setpoint device. This 
kit includes a cover that can be configured to 
conceal or expose the setpoint adjustments, setpoint 
indicator, and thermometer. Also, the kits can 
include an optional 1/2-inch large, exposed setpoint 
adjustment knob.  

Contents 

Part 

Quantity 

Retrostat Cover Kit 

Thermostat * 

Hardware kit  

Optional 1/2-Inch Large, Exposed 
Setpoint Knob  

Adapter Frame (192-308) 

*  Includes thermostat installation instructions.  

Product Numbers 

Retrostat Kit  

(See Notes below) 

Type 

192-840 

Direct Acting Fahrenheit Scale 

192-841 

Reverse Acting Fahrenheit Scale 

192-850 

Direct Acting Celsius Scale 

192-851 

Reverse Acting Celsius Scale 

NOTES: 

1.  Includes all parts needed for all conversions 

listed in Table 1 including installations where a 
large rough-in hole must be covered. These 
installations may require an adapter frame 
(192-308). 

2.  For Retrostat Kits with white cover, order the 

standard kit with “W” suffix.  

3.  For Retrostat Kits with optional 1/2-inch large, 

exposed setpoint adjustment knob, order the 
standard kit with “K” suffix.  

Required Tools 

 

Calibration and cover screw wrench 
(192-632) or 1/16” Allen wrench and 1/8” 
open-end wrench 

 

Medium flat-blade screwdriver 

 

Small level 

 

Accurate thermometer 

 

Needle nose pliers  

 

Prerequisites  

 

Review all of these instructions before you 
begin installation.  

 

Check job drawings for any site-specific 
information.  

 

Verify that the existing thermostat installation 
has its supply and return air lines connected 
properly.  

 

Make certain air supply is 18 to 25 psi 
(124 to 172 kPa) normal. 

 

Obtain the installation instructions provided 
with the thermostat in the Retrostat Kit. The 
document provides instructions for calibrating 
the thermostat.  

 

Make certain a supply of wall anchors and 
plastic ties are available.  

Expected Installation Time 

1 hour 

Summary of Contents for Retroline TH 192

Page 1: ...Acting Celsius Scale NOTES 1 Includes all parts needed for all conversions listed in Table 1 including installations where a large rough in hole must be covered These installations may require an adapter frame 192 308 2 For Retrostat Kits with white cover order the standard kit with W suffix 3 For Retrostat Kits with optional 1 2 inch large exposed setpoint adjustment knob order the standard kit w...

Page 2: ... for the application 3 Place the multi slotted metal plate into the plastic adapter frame plastic frame may or may not be required Attach the multi slotted plate to the terminal head or the wall using screws and slots shown in Figures 3 through 26 4 Loosely screw adapter base to the multi slotted plate 5 Draw plastic tubing through the multi slotted plate and the adapter base Install the plug in a...

Page 3: ... rough in holes 2 For replacement of thermostats not listed use the Powers Universal Adapter Kit 192 300 Powerstar Thermostat and Powerstar Thermostat Consult you local Siemens Building Technologies representative for details 3 Place the optional 1 2 inch large setpoint adjustment knob on the shaft protruding through the cover Use either the hex key end of the calibration and cover screw wrench or...

Page 4: ...nstructions provided with the thermostat in this retrostat kit for the following procedures Thermometer Calibration Changeover Point Adjustment Limit Stop Adjustment Sensitivity Adjustment Thermostat Cooling Heating Calibration Troubleshooting Reference Technical Bulletin Document Number TB 214 TH 192 Adapter Kits 155 231 Figure 1 Typical Thermostat Installation ...

Page 5: ...hrough the frame and into its respective hole Drive the expander nails to secure the frame in place To uninstall the frame remove the expander nails by turning them counterclockwise 3 Mount the cover over the frame and secure in place by turning each end locking screw five turns counterclockwise Figure 2 TH 192 Installation with Guard NOTE Adapter Frame Adapter Base and Plug in Adapter 2 not shown...

Page 6: ...llation NOTE Adapter Base and Plug in Adapter 2 not shown See Figure 1 for proper installation Figure 4 TH 180 TH 182 TH 192 Horizontal to Vertical Flush Installation NOTE Adapter Base and Plug in Adapter 2 not shown See Figure 1 for proper installation Figure 5 TH 180 TH 182 TH 192 Horizontal to Vertical Surface Installation ...

Page 7: ...129 116 Installation Instructions September 24 2009 Siemens Industry Inc Page 7 of 12 NOTE Plug in Adapter 2 not shown See Figure 1 for proper installation Figure 6 Honeywell TO900A TP900A Surface Box Installation ...

Page 8: ...ion NOTE Adapter Base and Plug in Adapter 2 not shown See Figure 1 for proper installation Figure 8 Honeywell TP910A B Flush Banjo Installation NOTE Adapter Base and Plug in Adapter 2 not shown See Figure 1 for proper installation Figure 9 Honeywell TO91A TP901A B Mortar Joint Installation NOTE Adapter Base and Plug in Adapter 2 not shown See Figure 1 for proper installation Figure 10 Honeywell TO...

Page 9: ...ter Base and Plug in Adapter 2 not shown See Figure 1 for proper installation Figure 12 Honeywell TP931B Flush Electrical Box Installation NOTE Retainer 2 Adapter Base and Plug in Adapter 2 not shown See Figure 1 for proper installation Figure 13 Honeywell TP970A B Shallow Wall Box with Plaster Ring Installation NOTE Retainer 2 Adapter Base and Plug in Adapter 2 not shown See Figure 1 for proper i...

Page 10: ...ter Base and Plug in Adapter 2 not shown See Figure 1 for proper installation Figure 16 Johnson T4002 Flush Box Installation NOTE Adapter Base and Plug in Adapter 2 not shown See Figure 1 for proper installation Figure 17 Johnson T400 401 402 Flush Fitting Installation NOTE If the terminal head is too close to the wall surface loop the plastic tubing around the multi slotted plate as shown in Figu...

Page 11: ...red Adapter Base and Plug in Adapter 2 not shown See Figure 1 for proper installation Figure 20 Robertshaw T15 T16 TP2210 Surface Fitting Installation NOTE Adapter Base and Plug in Adapter 2 not shown See Figure 1 for proper installation Figure 21 Robertshaw T15 T16 TP2210 Dry Wall Installation NOTE Adapter Base and Plug in Adapter 2 not shown See Figure 1 for proper installation Figure 22 Barber ...

Page 12: ...rkway Buffalo Grove IL 60089 4513 U S A Tel 1 847 215 1000 Your feedback is important to us If you have comments about this document please send them to sbt_technical editor us sbt siemens com Document No 129 116 Printed in U S A Page 12 of 12 NOTE Retainer 2 Adapter Base and Plug in Adapter 2 not shown See Figure 1 for proper installation Figure 23 Barber Colman TK1001 1002 1003 1101 1102 1103 90...

Reviews: