Connection
Application examples
6
A6V11545892_en--_a
137 | 150
6.3.3 Swap function and/or fan in the 2nd stage
2-pipe fan coil application for floor heating/cooling (2-stage heating/cooling), fan
runs only in the 2
nd
stage:
Commissioning
Outputs used
●
Fan P350 = 4 (2
nd
stage)
●
Valve P201 = 5 (floor)
●
Valve P203 = 5 (fan coil
unit)
●
M1 DC 0...10 V fan
●
V1 DC valve floor
●
V2 DC valve fan coil
units
140] for min. and
max. ratings
RDG260KN
Example 1:
Fan in the 2
nd
stage