32 / 46
Siemens
RDF300… / RDF340... / RDF400… / RDF600… Basic Documentation
CE1P3076.en
Smart Infrastructure
2020-02-21
3. Select the required parameter by repeatedly pressing b and -.
4. When you press b and - simultaneously, the current value of the
selected parameter starts to flash, which can be changed by repeatedly
pressing b or -.
5. When you again press b and – simultaneously, the next parameter is
displayed.
6. Repeat Steps 3 to 5 to display and change additional parameters.
7. All changes are saved and the controller returns to Protection 10 seconds after
the last display or setting.
The factory settings for the control parameters can be reloaded via parameter P71,
by changing the value to “ON”, and confirming by pressing buttons
+
and
–
simultaneously. The display shows “8888” during reload.
·
RDF400... and RDF600T: Step 1 is not required.
·
RDF3... and RDF600: Step 1 is required.
If one of the digital inputs is commissioned as window contact, and the contact is
closed, the controller will be switched to ECO mode and parameter setting will
not be possible. Solution: open the window contact.
#
Parameter
Factory
setting
Setting range
RDF3
00…
RDF6
00
RDF3
40…
RDF4
00…
RDF6
00T
Service Level
P01
Control sequence
2-pipe: [0..3]
1 (Cool only)
4-pipe: [2…4]
4 (Heat&Cool)
0:= Heating only
1:= Cooling only
2:= Manual H/C
3:= Auto changeover
4:= Heating & cooling
ü
ü
ü
P02
Mode selection via user operating mode button
1 (Stb, Comf)
1 = Stb,Comf
2 = Stb, Comf, Eco
ü
ü
ü
P04
Selection of °C or °F
°C (0)
(0) °C or
(1) °F
ü
ü
ü
P05
Sensor calibration
0.0 K
– 3 ... +3 K
ü
ü
ü
P06
Standard temperature display
0 (Room temp)
0:= Room temperature
1:= Setpoint
ü
ü
ü
P07
Additional user info
0 (no display)
0:= no display
1:= Temp in °C and °F
ü
ü
r
P08
Comfort basic setpoint
21 °C
5 ... 40 °C
ü
ü
ü
P09
Minimum setpoint limitation for Comfort
(WminComf)
5 °C
5 ... 40 °C
ü
ü
ü
P10
Maximum setpoint limitation for Comfort
(WmaxComf)
35 °C
5 ... 40 °C
ü
ü
ü
P11
Heating setpoint for Economy
(WheatEco)
15 °C
OFF, 5 °C…WcoolEco
ü
ü
ü
P12
Cooling setpoint for Economy
(WcoolEco)
30 °C
OFF, WheatEco…40 °C
ü
ü
ü
P13
Electrical reheater for cooling mode
ON
ON:= enabled
OFF:= disabled
ü
ü
ü
P14
Key lock
(Press the operating mode button
for 7 seconds
to enable or disable the key lock)
RDF600... : 3
seconds
0 (Unlocked)
0:= Unlocked
1:= Auto lock
2:= Manual lock
ü
ü
ü
·
P02 is not available when the controller is commissioned for manual
heating/cooling changeover P01=2
·
Parameter display depends on selected application and function
(x) Not available
Adjust parameters
Reset parameters
Note! *)
Control parameters
Note