background image

 

 

Installation Instructions

Document No. 129-497

May 18, 2011

 

RDF Series Room Temperature 
Controllers 

 

 

Item Number 129-497, Rev. BA

 

Page 1 of 7 

Product Description 

Room Temperature Controllers with LCD for two-
pipe (with and without an electrical heater) and four-
pipe fan coil units. 

Product Numbers 

Part Number 

Application 

RDF10U 

Two-pipe fan coil units 

RDF20U 

Two-pipe fan coil units with 
electrical heater 

RDF30U 

Four-pipe fan coil units 

RDF50.1U 

Two-pipe fan coil units with 0 to 10 
Vdc output 

Required Tools 

 

Small, flat-blade screwdriver 

 Wire 

strippers 

 Electric 

drill 

Expected Installation Time 

30 minutes 

Accessories 

 

141-570 Lockable Thermostat Guard 

 

ARG70 Wall Plate Adapter 

 QAH11.1 

Remote/Changeover 

Sensor 

 

Installation 

 

Step 1. Loosen retaining screws. 

 

Step 2. Remove controller housing. 

 

Step 3. Mount base plate to wall

 

Step 4.  Remove screw and open terminal cover. 

Summary of Contents for RDF10U

Page 1: ...pe fan coil units RDF20U Two pipe fan coil units with electrical heater RDF30U Four pipe fan coil units RDF50 1U Two pipe fan coil units with 0 to 10 Vdc output Required Tools Small flat blade screwdriver Wire strippers Electric drill Expected Installation Time 30 minutes Accessories 141 570 Lockable Thermostat Guard ARG70 Wall Plate Adapter QAH11 1 Remote Changeover Sensor Installation Step 1 Loo...

Page 2: ...ur pipe system TH0899R1 S1 M1 Y1 I II III SN SP SN 1 3 7 8 D1 GND 4 2 10 11 12 N1 9 B2 B1 5 Figure 1 RDF10U TH0897R1 S1 B1 M1 Y1 I II III SN SP SN 1 3 9 8 D1 GND 4 2 10 11 12 N1 Y2 6 5 Figure 2 RDF30U Terminal Position RDF10U and RDF30U Terminal Function 1 Operating voltage 24 Vac negative 2 Operating voltage 24 Vac negative 3 Operating voltage 24 Vac positive 4 Heating cooling output NO 5 Heating...

Page 3: ...ND Signal input for potential free operating mode changeover switch TH0896R1 S1 B2 M1 Y1 I II III SN SP SN 5 7 2 3 D1 Siemens Industry Inc Page 3 of 7 G 1 6 N1 10 11 12 ND B1 4 Figure 4 RDF50 1U 3 2 T F 3 2 3 2 T 3 2 QAH11 1 T F T F TH0890R1 Figure 5 RDF50 1U Terminal Position RDF50 1U Terminal Function 1 0 to 10 Vdc output for valve 2 Heat Cool changeover sensor 3 Measuring neutral 4 Return air s...

Page 4: ...t is made The display will then stop flashing Changing from Heating to Cooling Mode Automatic changeover Display shows that heating valve is open Display shows that cooling valve is open Selecting the Three Fan Speeds with the Operating Mode Selector High Medium Low Changing from Heating or Cooling Mode to Standby With all RDF types the operating mode selector is used to manually change from Heati...

Page 5: ... be adjusted Adjustments can be made during operation without opening the controller If the room temperature displayed by the controller does not agree with the actual room temperature the temperature sensor can be recalibrated by changing parameter P09 NOTE For factory settings see Commissioning See Changing the Control Parameters and follow steps 1 through 3 to select parameter P09 With step 4 t...

Page 6: ...Fan control is temperature dependent in all operating modes 2 Temperature or setpoint display Room or return air temperature display Setpoint display 3 Operating action of switch for external operating mode changeover Changeover is activated when switch is closed NO Changeover is activated when switch is open NC RDF20U 4 Electrical heater Active in cooling mode Inactive in cooling mode 1 Fan contr...

Page 7: ...alibration 0 0 K 3 K to 3 K 5 5 F to 5 5 F Not adjustable display only P10 Switching differential in heating mode 2 K 3 6 F 1 F to 7 F 0 5 K to 4 K x Not adjustable no display P11 Switching differential in cooling mode 1 K 1 8 F 1 F to 7 F 0 5 K to 4 K Integration time 5 minutes 1 to 10 minutes X X X P12 Dead zone in normal operation 2 K 3 6 F 1 F to 18 F 0 5 K to 10 K X X X P13 Active temperature...