background image

 

 

Installation Instructions 

Document No. 129-084 

September 16, 2015

 

RC 195 Receiver-Controller Restrictor 
and Connector Repair 

 

 

Item Number 129-084, Rev. DA

 

Page 1 of 3 

Product Description 

The Restrictor Kit contains three input restrictor 
assemblies, one supply restrictor assembly and 
seven gaskets. 

The Connector Kit contains one supply connector 
assembly and one input connector assembly. 

Product Numbers 

Restrictor Kit 

195-066 

Connector Kit for Multiple Input 

195-067 

Receiver-Controller 

Connector Kit for Single Input 

195-114 

Receiver-Controller 

Required Tools 

 

Small, flat-blade screwdriver 

NOTE: 

Normally, replacing restrictors or connectors 
will not affect calibration.

 

Before troubleshooting (Table 1), ensure that: 

1. 

The supply pressure at the unit is constant 
(± 2 psi) 22 psi (152 kPa). 

2. 

All transmitter inputs being used are between

  

3 and 15 psi (21 and 103 kPa). 

3. 

Only one restrictor (internal or external) 
supplies

 

each transmitter. 

4. 

The transmitter calibration is correct. 

Troubleshooting 

Table 1.  Troubleshooting Guide. 

Problem 

Check 

Probable Cause  

Corrective Action 

Control pressure 
stays at 
approximately zero 

Rotate setpoint 
adjustment screw 
counterclockwise 

Pressure 
increases 

Transmitter sensing medium 
which is above (R.A.) or below 
(D.A.) the proportional band 

None 

RC 195 out of calibration 

Recalibrate 

Pressure 
remains 
unchanged 

Plugged supply restrictor 

Replace supply restrictor 

Plug-in connector defective 

Replace plug-in connector 

Receiver-controller is 
defective 

Replace receiver-controller 

Control pressure 
stays at 
approximately 
supply pressure 

Rotate setpoint 
adjustment screw 
clockwise 

Pressure 
decreases 

Transmitter sensing medium 
which is above (D.A.) or below 
(R.A.) the proportional band  

None 

RC 195 out of calibration 

Recalibrate 

Pressure 
remains 
unchanged 

Receiver-controller is 
defective 

Replace receiver-controller 

Transmitter 
pressure stays at 
approximately zero 

Increase sensed 
medium to upper end 
of transmitter range 

Pressure 
remains 
unchanged 

Plugged input restrictor 

Replace input restrictor 

No restrictor supplying 
transmitter 

Place restrictor in the "in"' 
position 

Defective transmitter 

Replace transmitter 

Transmitter 
pressure will not 
build up to 15 psi 
(103 kPa) 

Increase sensed 
medium to upper end 
of transmitter range 

Pressure still will 
not build up to 
15 psi (103 kPa) 

Leak at or defective plug-in 
connector  

Replace plug-in connector 

Defective transmitter  

Replace transmitter 

Low supply pressure  

Increase supply pressure 

Reviews: