Wall-mounted sensors and room operator units for KNX/ETS and KNX/ACS
CM2N1602en_05
Building Technologies
ETS engineering
2018-09-14
5.5 ETS parameter description
Factory settings are in brackets
Designation
Values
Type
Communication objects available in ETS
when function is enabled
Range
(
Default
)
Un
it
Q
M
X3
.P3
0
Q
M
X3
.P4
0
Q
M
X3
.P7
0
Q
M
X3
.P3
4
Q
M
X3
.P7
4
Q
M
X3
.P3
7
Q
M
X3
.P0
2
5.5.1 Room temperature sensor
Room temperature: Sensor correction
–5…+5 °C
in 0.1 steps
(0 °C)
K
X X X X X X X
Room temperature: Send following change by
0.1…2.5 °C
(0.1 °C)
K
X X X X X X X
Room temperature: Send cyclically after
1…60
(2 min)
min
X X X X X X X
5.5.2 Room temperature control
To display this section, enable the option “Activate room temperature control” in
Device
Activate room temperature control
yes; no
X X X X X X X
Heating type*
Radiator heating slow
(
Radiator heating fast)
Floor heating slow
Floor heating fast
X X X X X X X
Cooling type
(
Chilled ceiling
)
Floor cooling
X X X X X X X
Parameters heating / cooling type allow for adapting the controller to
the type of heating / cooling. In addition, the controller features two
control algorithms: one for continuous mode (0..100%) and one for
PWM mode (On/Off). The mode is selected via parameter "Control
value type". The control value type is identical for all operating modes.
In continuous mode, the associated PWM output is "On" at
continuous control value ≠ 0.
In PWM mode, cycle time and pulse width are adapted to the type of
heating / cooling, the setpoint, and the measured room temperature.
The min. cycle time is 12 minutes, the min. pulse width is 4 minutes.
The continuous control value issues 0% or 100% in this operating
mode.
Default heating setpoint
5…40
(21.0)
°C
X X X X X X X
Default cooling setpoint
5…40
(24.0)
°C
X X X X X X X
Control value type
(
PWM)
Continuous 0…100%
X X X X X X X
Send cyclically after
Do not send cyclically
1;2;3...30;45;60
min
X X X X X X X
Protection heating setpoint
5…40 (12.0)
°C
X X X X X X X
Economy heating setpoint
5…40 (15.0)
°C
X X X X X X X
Precomfort heating setpoint
5…40 (19.0)
°C
X X X X X X X
Comfort heating setpoint
5…40 (21.0)
°C
X X X X X X X
Comfort cooling setpoint
5…40 (24.0)
°C
X X X X X X X
Precomfort cooling setpoint
5…40 (28.0)
°C
X X X X X X X
Economy cooling setpoint
5…40 (35.0)
°C
X X X X X X X
Protection cooling setpoint
5…40 (40.0)
°C
X X X X X X X
Comfort extension time
5…120 (30)
min
X X X X X X X
Number of window status inputs
0…4
X X X X X X X