Siemens QFM81.21 Installation Instructions Download Page 1

 

 

Installation Instructions

Document No. 129-606 

July 15, 2010

 

QFM81.2, QFM81.21 Duct Hygrostats 

 

 

Item Number 129-606, Rev. AA

 

Page 1 of 2 

Product Description 

These instructions explain how to install a QFM81.2 
or QFM81.21 Duct Hygrostat. 

Product Numbers 

QFM81.2 Duct Hygrostat with external setpoint 

QFM81.21 Duct Hygrostat 

Required Tools 

 Screwdriver 

 Electric 

drill 

 

7 mm Wrench 

Expected Installation Time 

15 minutes 

Installation 

Air Duct Mounting 

If the duct hygrostat is used for control, mount in the 
exhaust air duct after the room to be controlled.  

If the duct hygrostat is used for monitoring the 
maximum or minimum humidity level, mount in the 
supply air duct. 

Mounting Positions 

The immersion sensor stem must be mounted either 
horizontally or vertically with the stem pointing 
downward. Do not mount with the stem pointing 
upward. (See Figure 1.) 

SEN0508R1

 

Figure 1.  Acceptable Mounting Positions. 

Ensure that the air to be measured is sufficiently 
mixed at the point of measurement for accurate 
humidity measurements. 

The mounting orientation is dependent on the air 
velocity in the ductwork: at < 5 m/s, the holes in the 
stem must face the airflow; at > 5 m/s, they must be 
perpendicular to the direction of airflow. (See 
Figure 2.) 

SEN0509R1

< 5 m/s

> 5 m/s

 

Figure 2.  Mounting Orientations. 

Minimum Immersion Length 

NOTE: 

When mounting the hygrostat in air ducts, 
the minimum immersion length of the stem 
is 5.12 inches (130 mm).  

The mounting flange supplied with the unit allows 
the immersion length to be adjusted between 
5.12 inches (130 mm) and 6.14 inches (156 mm). 

 

Figure 3.  Mounting Flange. 

 