Siemens QFM3100 Installation Instructions Manual Download Page 1

 

 

Installation Instructions 

Document No. 129-413 

October 5, 2009 

 

Q-Series Relative Humidity (RH) and 
Relative Humidity & Temperature (RH/T) Duct Sensors 

 

 

Item Number 129-413, Rev. CA

 

Page 1 of 3 

Product Description 

Relative Humidity (RH) and Relative Humidity & 
Temperature (RH/T) duct sensors monitor the 
relative humidity or the relative humidity and 
temperature in a duct, depending on the model. 

Sensors are directly wired to the controller via 
twisted pair and/or three conductor cables  
(18 to 22 AWG). The number and type of cables 
required depends on the model selected. All field 
wiring is terminated in a terminal block on the sensor 
body. 

Product Numbers 

Table 1.  Relative Humidity Only. 

Product 
Number 

Humidity 

Signal 

Accuracy

 

QFM2100

 

0 to 10 Vdc

 

±5% 

QFM3100

 

±2% 

QFM2101

 

4 to 20 mA

 

±5% 

QFM3101

 

±2% 

QFM4101

 

±2% Certified 

Table 2.  Relative Humidity and Temperature. 

Product 
Number 

Temperature 

Signal 

Humidity 

Signal 

Accuracy

 

QFM2160

 

0 to 10 Vdc

 

0 to 10 Vdc

 

±5% 

QFM3160

 

±2% 

QFM3160D 
QFM4160

 

±2% Cert. 

QFM2171

 

4 to 20 mA

 

4 to 20 mA

 

±5% 

QFM3171

 

±2% 

QFM3171D 
QFM4171

 

±2% Cert. 

QFM2110

 

Pt 1K

 

0 to 10 Vdc 

±5% 

QFM2120

 

Ni 1K

 

QFM3110

 

Pt 1K

 

±2% 

♦ 

Applies to humidity only

 

NOTE: 

Sensor tips on QFM31… and QFM41… 
models are field replaceable. 

Additional Reference Documents 

Product Number 

Technical Instructions 

QFM21… 

155-748 

QFM3160 

155-749 

QFM4160 

155-750 

Required Tools 

 

Phillips screwdrivers, No. 1 and No. 2 

 

Wire cutters/strippers 

 

Medium flat-blade screwdriver 

 

Tape measure 

 

Medium-duty electric drill 

 

Marker or pencil 

 

No. 26 (0.147-inch) drill bit 

 

Small level 

 

7/8-inch drill bit or hole saw 

 

Two No. 8 × 1-inch sheet metal screws 

Expected Installation Time 

One hour 

Prerequisites 

 

Ensure that the appropriate field wiring is 
installed. 

Appropriate wiring is one or more twisted 
pairs, or three conductor cables (plenum or 
non-plenum as required), within the maximum 
wiring run length for the individual equipment 
controller. The maximum recommended 
length is 750 feet (229 m). 

 

Ensure that all wiring complies with National 
Electric Code (NEC) and local regulations. 

Mounting Information 

Locate the sensor: 

 

In the center of a duct. 

 

Away from fans, corners, heating and cooling 
coils, and so on. 

 

Where it receives adequate airflow for proper 
operation. 